ANALISA OVER CURRENT RELAY (OCR) PADA TRANSFORMATOR DAYA 60 MVA DENGAN SIMULASI MATLAB DI GARDU INDUK PAYA GELI

  • Siti Anisah Universitas Pembangunan Panca Budi
  • Dwi Putri Wardani Universitas Pembangunan Panca Budi
  • Rahmaniar Rahmaniar Universitas Pembangunan Panca Budi
  • Hamdani Hamdani Universitas Pembangunan Panca Budi

Abstract

The distribution of electrical energy properly many aspects that need to be considered is the reliability of the protection system. To maintain the reliability of electrical equipment, especially transformers, a protection system is needed. A protection system is a system that functions to prevent or limit damage to equipment as a result of interference. One type of protection used is Over Current Relay (OCR). Where the working principle of the OCR is to detect the presence of overcurrent that exceeds the predetermined setting value, whether caused by a short circuit between phases or overload. In this paper, describes the use of the electric circuit method. The simulation of this electric circuit method uses Matlab as a verification calculation. The results of the calculation of the inter-phase fault current that occur, the largest value of short circuit fault currents between phases is located at 0% point of 8113.79 Ampere and the smallest value of short circuit fault currents between phases is at 100% point of 1208.10 Ampere and comparison with experiments using the matlab application obtained results that are not too far from the results of manual calculations

References

Agung, A. I. (2014). Proteksi Sistem Tenaga Listrik. Surabaya: Universitas Negeri Surabaya. Irfan, A. (2009). Analisa setting relay arus lebih pada penyulang sadewa. Jakarta: Universitas Indonesia.
Aryza, S. (2018). a Novelty of Quality Fertilizer Dryer Based on Solar Cell and Ann.
Kamal. A, S. d. (2014). Optimal Over Current Relay Coordination of a Real Time Distribution System with Embedded Renewable Generation.
Kustanto, H. Y. (2014). Analisis OCR (Over Current Relay) dan GFR (Ground Fault Relay) Pada Transformator Daya 1 (60 MVA) Gardu Induk Bantul 150 Kv Menggunakan Program Etap. Jurnal Elektrical, Volume 1 No.1. Hal 58-68.
Pranayuda, F. S. (2012). Analisis penyetelan proteksi arus lebih penyulang cimalaka di gardu induk 70 Kv sumedang. Jurnal media elektrika.
Sarimun, W. (2012). Proteksi Sistem Distribusi Tenaga Listrik. Jakarta: Garamond. Sianipar, D. E. (2017). Matlab untuk aljabar linier dan matriks. Yogyakarta: Andi.
Rahmaniar, R. (2019). Model FLASH-NR Pada Analisis Sistem Tenaga Listrik (Doctoral dissertation, Universitas Negeri Padang).
Tarigan, A. D., & Hamdani, H. (2020, September). Penggunaan Sistem Pendingin Temperatur Sebagai Peningkatan Kinerja Panel Surya. In Seminar Nasional Teknik (SEMNASTEK) UISU (Vol. 3, No. 1, pp. 121-127).
Tarigan, A. P. (2020). Perancangan Pembangkit Gelombang Ultrasonic Variabel Menggunakan Mikrokontroler Atmega 16. In Seminar Nasional Teknologi Informasi & Komunikasi Ke-7 (Vol. 1, No. 1, pp. 327-333).
Wibowo, P. (2018). Perancangan Sistem Keamanan Rumah Menggunakan Sensor Pir Berbasis Mikrokontroler. Jurnal Elektro dan Telkomunikasi, 4(2), 36-43.
Published
2021-03-12
How to Cite
ANISAH, Siti et al. ANALISA OVER CURRENT RELAY (OCR) PADA TRANSFORMATOR DAYA 60 MVA DENGAN SIMULASI MATLAB DI GARDU INDUK PAYA GELI. Scenario (Seminar of Social Sciences Engineering and Humaniora), [S.l.], p. 262-270, mar. 2021. Available at: <https://jurnal.pancabudi.ac.id/index.php/scenario/article/view/1193>. Date accessed: 22 dec. 2024.
Issue
Section
Articles